NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
3 Installation Guide
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
56
Figure 3-37
Connecting the teamwork cable
Connecting Monitoring Cables
NetCol8000-A013 supports RS485 monitoring.
If there is no teamwork networking, connect the smart cooling products hand-in-hand
and connect the CN17 port on the first smart cooling product to the monitoring device.
An ≤ 255.
In teamwork networking, connect the CN17 port on the first smart cooling product in the
teamwork networking to the monitoring device. An ≤ 32.
Considering the monitoring speed, it is recommended that An be less than or equal to 8.
Figure 3-38
Connecting the RS485 monitoring
3.11.6 Cable Routes
The bottom routing for power cables and the signal cable between indoor and outdoor units is
shown in the figure.