NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
E Controller Menu
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
169
Menu
Name
Default
Value
Settings Range
Humid P-band
5.0%
1.0% to 90.0%
Humid Dead zone
1.0%
0.5% to 90.0%
Setting
>
Admin Menu
>
System Setting
>
Compressor
Min Run Time
180s
120s to 600s
Min Stop Time
180s
120s to 600s
Min Speed
1200rpm
1200 rpm to 4800 rpm
Max Speed
4800rpm
1200 rpm to 4800 rpm
Oil Return Cycle
180s
120s to 600s
Forced Oil Return Cycle
2h
2h to 24h
Oil Return Speed
3000rpm
From Min Speed to
Max Speed
Stop Vacuum Speed
1800rpm
From Min Speed to
Max Speed
Stop Vacuum Pressure
0.48 MPa
0 to 1.5 MPa
Comp Preheating
On (The
default value
is On for the
first startup
and the value
is Off after
preheating is
complete.)
On/Off
Dis HT Rise Limit Temp
97.0°C
90°C to 115°C
Dis HT Drop Temp
107.0°C
90°C to 115°C
Setting
>
Admin Menu
>
System Setting
>
Indoor Fan
Min Speed
30%
30% to 100%
Max Speed
100%
30% to 100%
Dehumid Speed
80%
Minimum value:
(Maximum speed of the
indoor fan – 30%) or
minimum speed of the
indoor fan, take the
smaller value
Maximum value:
maximum speed of the
indoor fan
Min S/R Air Temp Diff
5.0°C
1.0°C to 20.0°C
Max S/R Air Temp Diff
10.0°C
1.0°C to 20.0°C
Start Delay
30s
0 to 99s