Alarm
ID
Alarm Name System
Action
Possible Causes
Solution
(The alarm
needs to be
manually
cleared.)
a specified period of time.
605
OutFan1 Fault
The
compressor
shuts down.
1.
Outdoor fan 1 is blocked.
2.
The condenser fins are dirty
or blocked.
3.
The outdoor unit is in the
headwind or downwind
state.
4.
Outdoor fan 1 is faulty.
1.
Check that outdoor fan 1 is
not blocked.
2.
Clean the condenser fins.
3.
Add air baffles.
4.
Replace outdoor fan 1.
606
OutFan2 Fault
The
compressor
shuts down.
1.
Outdoor fan 2 is blocked.
2.
The condenser fins are dirty
or blocked.
3.
The outdoor unit is in the
headwind or downwind
state.
4.
Outdoor fan 2 is faulty.
1.
Check that outdoor fan 2 is
not blocked.
2.
Clean the condenser fins.
3.
Add air baffles.
4.
Replace outdoor fan 2.
607
OutFan1
Speed
Abnormal
Alarm
The
compressor
shuts down.
1.
The outdoor unit is not
properly installed.
2.
The outdoor unit is in the
strong wind state.
3.
Outdoor fan 1 is faulty.
1.
Reinstall the outdoor unit.
2.
Add air baffles.
3.
Replace outdoor fan 1.
608
OutFan2
Speed
Abnormal
Alarm
The
compressor
shuts down.
1.
The outdoor unit is not
properly installed.
2.
The outdoor unit is in the
strong wind state.
3.
Outdoor fan 2 is faulty.
1.
Reinstall the outdoor unit.
2.
Add air baffles.
3.
Replace outdoor fan 2.
701
Discharge
Press Sensor
Fault
The
compressor
shuts down.
1.
The pressure sensor cable is
not properly connected.
2.
The pressure sensor is
faulty.
1.
Check the cable connection
to the pressure sensor.
2.
Maintain or replace the
pressure sensor.
702
Suction Press
Sensor Fault
The
compressor
shuts down.
1.
The pressure sensor cable is
not properly connected.
2.
The pressure sensor is
faulty.
1.
Check the cable connection
to the pressure sensor.
2.
Maintain or replace the
pressure sensor.
703
Suction Temp
Sensor Fault
The
compressor
shuts down.
1.
The temperature sensor
cable is not properly
connected.
2.
The temperature sensor is
faulty.
1.
Check the cable connection
to the temperature sensor.
2.
Maintain or replace the
temperature sensor.
704
Discharge
Temp Sensor
Fault
--
1.
The temperature sensor
cable is not properly
connected.
2.
The temperature sensor is
faulty.
1.
Check the cable connection
to the temperature sensor.
2.
Maintain or replace the
temperature sensor.