NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
5 System Operation and Maintenance
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
88
Alarm
ID
Alarm Name System
Action
Possible Causes
Solution
module of the compressor
drive board is faulty.
213
Comp Start
Fail Alarm
The
compressor
shuts down.
The difference between the
compressor control output
rotational speed and the actual
compressor rotational speed is
greater than the control
threshold.
1.
Check the compressor
status.
2.
Refill refrigerant.
3.
Replace the compressor
drive board or compressor.
214
Comp Drive
DC Overvolt
Alarm
The
compressor
shuts down.
The input voltage of the
compressor drive board is
higher than the preset threshold.
1.
Check whether the input
power is within the normal
range.
2.
Use an oscilloscope to check
whether the waveform of the
power grid is within the
normal range.
3.
Replace the compressor
drive board if it is faulty.
215
Comp Drive
DC Undervolt
Alarm
The
compressor
shuts down.
The input voltage of the
compressor drive board is lower
than the preset threshold.
1.
Check whether the input
power is within the normal
range.
2.
Use an oscilloscope to check
whether the waveform of the
power grid is within the
normal range.
3.
Replace the compressor
drive board if it is faulty.
216
Comp Drive
Overheat
Alarm
The
compressor
shuts down.
Protection against overheating
of the compressor drive board is
triggered.
1.
Check whether the fan speed
of the outdoor unit is
normal.
2.
Check whether refrigerant in
the system is insufficient,
which causes the outdoor
unit fan to operate at a low
speed.
3.
Check the installation
environment of the outdoor
unit to see whether the heat
dissipation of the outdoor
unit is poor and whether the
outdoor unit is blocked.
4.
Check whether the fins of
the outdoor unit are
polluted, which causes the
air intake volume of the
outdoor unit to be small.
217
Comp Drive
Alarm
The
compressor
shuts down.
The compressor drive board of
the outdoor unit is faulty.
1.
Check the compressor
status.
2.
Check the connection status
of the compressor and the