GSC53N - GSC57 - ZG47
EN - 86
8.4.3. "HARM" mode
Selecting the HARM mode one of the below screens will be displayed according to the
settings made as per paragraph 8.12. The screens show the harmonics (see paragraph
17.11) of the phase or phase-to-phase voltage.
Example of screen in single-
phase system
Example of screen in “3 wires”
three-phase system
Example o
f screen in “4 wires”
three-phase system
The symbols used are described in Table 7
For any message displayed see Appendix 1 – MESSAGES DISPLAYED.
The displayed histograms represent the harmonic content of the voltage under test. The
value of the first harmonic h01 (fundamental at 50Hz) is not represented in scale along
with the other harmonics in order to maximize the display of the latter. In case both voltage
and current are connected to the instrument inputs, eventual negative values of the
harmonics (therefore represented under the horizontal axis), indicate that such voltage
harmonics are “generated” by the load.
Following keys are enabled:
F3
,
F4
:
to move the cursor of the selected harmonic leftwards and rightwards
respectively. At the same time the values relevant to the order no. of
the selected harmonic and to the corresponding absolute and relative
values (calculated on the basis of the fundamental) are updated.
F1
(only for three-phase mode): to display the values of the harmonics
of the other voltages available. The voltage displayed is indicated
above the F3 key.
F2
:
to display the page of the harmonics h01 h24 (symbol
h24
) or that
of the harmonics h25 h49 (symbol
h49
).
ESC
:
to return back to METER mode (see paragraph 8.4.2).
SAVE
:
to save in the instrument memory a record of “Smp” type (see paragraph
9.2) and the instantaneous values of voltage and current present on the
instrument inputs. This function is disabled during a recording.
ENTER/HOLD
: to enable/disable the HOLD function (updating interruption) of the
displayed data. All the previous functions remain however available.
When the HOLD function is enabled, the word
HOLD
is displayed.
When this function is enabled it’s not possible to record or take an
energy measurement. This function is disabled during a recording or
an energy measurement.
MENU
:
to enter in the
MENU
mode and change the instrument settings (see
paragraph 8.1 and 8.2). It’s not possible to enter the configuration
MENU during a recording or an energy measurement.
START/STOP
: to record
selected parameters
according to the instrument’s settings
(see chapter 10).
27.09.00 17:35:12
V1 = 230.2 V
h03 = 10.2 V
h03 = 4.3 %
ThdV = 11.0 %
h49
27.09.00 17:35:12
V12 = 400.2 V
h03 = 14.2 V
h03 = 3.5 %
ThdV = 11.0 %
ChgP
h49
27.09.00 17:35:12
V1 = 230.2 V
h03 = 10.2 V
h03 = 4.3 %
ThdV = 11.0 %
ChgP
h49