MEASURING PROCEDURES
8.8.1. Using the Instrument in a Single Phase System
WARNING
The maximum voltage between B1 and B4 inputs is 600 V~ (CATII) / 350V~
phase – earth or 600V~ (CATIII) / 300 V~ phase to earth.
Do not measure voltages exceeding the limits prescribed by this manual.
Should you exceed the voltage limits you could damage the instrument
and/or its components or endanger your safety.
Phase
Neutral
B1
B2
B3
B4
I3
I2
I1
I1
Instrument connection in a single-phase system
WARNING
If possible, before connecting the instrument to the electrical equipment to
be tested take the power supply off the electrical equipment.
1. Check, and if needed modify, the basic settings of the instrument (see paragraphs 8.1
and 8.2). Particularly, the
single-phase
mode must be set.
2. Select the working mode corresponding to the type of analysis desired. In case of
doubts select the
POWER
working mode (see paragraph 8.6).
3. Connect the phase and neutral voltage wires respecting the connections shown in the
picture.
4. If you want to measure current and power, connect the clamp meter to the phase
conductor respecting the specifications shown on the clamp and the connections
shown in the picture.
In case of doubts select the
POWER
working mode and check if the active power P is
positive. If it’s negative, remove current transducer from the wire and reconnect it so
the transducer label faces the opposite direction.
5. Apply voltage to the electrical equipment under test (if previously shut off for the
instrument connection).
6. The values of the available electrical parameters will be displayed on the display of the
instrument. For further details see the paragraph relevant to the position of the switch.
7. You can press
HOLD
to interrupt the updating in real time of the displayed values.
8. You can press
SAVE
to save the displayed values (see paragraph 9.2).
9. If you want to record:
a) Check, and if needed modify, the values of the basic parameters (see par. 8.1 and 8.2).
b) Check, and if needed modify, the recording parameters by pressing
MENU
(see the
paragraph corresponding to the position of the rotary switch selected).
c) To start the recording press
START
(see chapter 10.1).