Shenzhen Hpmont Technology Co., Ltd.
Chapter 6 Function Introduction
HD5L Series Controller User Manual V1.4
―
77
―
Fault history (F17.11 - F17.27)
Ref. Code
Function Description
Setting Range [Default]
F17.11
Five times fault type
[Actual value]
F17.12
Setting freqency at the recent fault
F17.13
Output freqency at NO.5 fault
F17.14
DC bus vlotage at NO.5 fault
F17.15
Output voltage at NO.5 fault
F17.16
Output current at NO.5 fault
F17.17
Input terminal status at NO.5 fault
F17.18
Output terminal status at NO.5 fault
F17.19
NO.5 fault interval
F17.20
NO.4 fault type
F17.21
NO.4 fault interval
F17.22
NO.3 fault type
F17.23
NO.3 fault interval
F17.24
NO.2 fault type
F17.25
NO.2 fault interval
F17.26
NO.1 fault type
F17.27
NO.1 fault interval
F17.12 - F17.19 record status parameters of HD5L at the last fault.
F17.20 - F27 record the type and interval per time of four faults before the latest. The unit of interval is 0.1
hour.
6.2.19
F18: PWM Parameters
Ref. Code
Function Description
Setting Range [Default]
F18.00
Carrier frequency
1 - 16kHz [Depend on HD5L]
Defines the carrier frequency of PWM output wave.
Controller power
Setting range
Factory setting
0.2 - 22kW
1 - 16kHz
8kHz
30 - 45kW
1 - 12kHz
6kHz
1234
•
The carrier frequency will affect the operating noise of the motor. The higher the carrier frequency, the
lower the noise made by the motor. Please properly set the carrier frequency.
•
When the value is higher than the factory setting, HD5L should be derated by 5% when per 1kHz is
increased compared to the factory setting.
F18.01
Carrier freqency auto adjust selection
0,1 [0]
F18.02
PWM overmodulation enable
0,1 [1]
0:
Disable.
1: Enable.
F18.03
PWM overmodulation mode
0,1 [0]
0: Two phase / Three phase swtich.
1: Three phase.
6