Chapter 4 Electrical Installation
Shenzhen Hpmont Technology Co., Ltd.
―
22
―
HD5L Series Controller User Manual V1.4
4.4.5
Control Terminal Wiring
To reduce the interference and attenuation of control signal, length of control cable should limit within
50m. There should be more than 0.3m between the control cable and the motor cable.
The control cable must be shielded cable. The analogue signal cable must be shielded twisted pair.
Figure 4-6 HD5L control board connection
Digital Input Connection
Dry contact
Using the internal 24V power supply (SEL and P24 are short-connected at factory) or external power
supply (remove the connector between SEL and P24), their connections are shown in Figure 4-7.