Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
―
76
―
HD5L Series Controller User Manual V1.4
Input and output phase loss fault (F17.03 - F17.06)
Ref. Code
Function Description
Setting Range [Default]
F17.03
The detection base of lack of input
0 - 100 [30%]
F17.04
The detection time of lack of input
0.0 - 5.0 [1.0s]
F17.03 is a percentage of rated voltage of HD5L.
When HD5L detects certain input voltage does not hit the detection base (F17.03) and exceeds the preset
detection time (F17.04), HD5L alarms E0015 fault (lack of input).
•
F17.03 or F17.04 = 0 or in the battery driven run mode, HD5L will not detect input phase loss fault.
F17.05
The detection base of lack of output
0 - 100 [20%]
F17.06
The detection time of lack of output
0.0 - 20.0 [3.0s]
F17.05 is a percentage of rated current of HD5L.
When HD5L detects certain output current does not hit the detection base (F17.05) and exceeds the
detection time (F17.06), HD5L alarms E0016 fault (lack of output).
•
F17.05 or F17.06 = 0, HD5L will not detect output phase loss fault.
Motor fault (F17.07)
Ref. Code
Function Description
Setting Range [Default]
F17.07
Motor overload protect factor
20.0 - 110.0 [100.0%]
The motor overload protection factor can be set as 100% when HD5L drives a motor of the same power
class.
To protect the motor when the motor power is smaller than the standard matched power, user needs to set
proper motor overload protection factor (F17.07). The factor can derive from the following formula:
Motor
overload protect factor F17
.
07
Rated
current of motor F07
.
02
/
F10
.
03
Rated
output current of HD5L
100%
Fault auto-reset function and fault relay action (F17.08 - F17.10)
Auto reset function enables HD5L to reset the fault as per the preset times and interval.
The following faults do not have the auto reset function:
E0008: Power module fault
E0021: Read / Write fault of control board EEPROM
E0010: Brake unit fault
E0023: Read / Write fault of keypad EEPROM
E0013: Soft start contactor failed
E0024: External fault
E0014: Current detection fault
E0036: Contactor fault
Ref. Code
Function Description
Setting Range [Default]
F17.08
Fault auto reset times
0 - 100 [0]
F17.09
Fault auto reset interval
2.0 - 20.0 [5.0s/times]
When F17.08 = 0, it means “auto reset” is unused and the protective device will be activated in case of fault.
•
If no other fault is detected within 5 minutes, the auto reset count will be automatically cleared.
•
On condition of external fault reset, auto reset count will be cleared.
F17.10 Faulty
relay
action
00 - 11 [00]
Units: In auto reset process
•
0: Faulty relay doesn’t act.
•
1: Faulty relay acts.
Tens: In undervoltage process
•
0: Faulty relay doesn’t act.
•
1: Faulty relay acts.
Note: Relay needs to be set as No. 14 function. (Controller fault)