Shenzhen Hpmont Technology Co., Ltd.
Appendix A Parameters
HD31 Series User Manual V1.1
―
85
―
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
Hundreds: Overload detection
threshold
0: Relates to rated current of
motor (alarm E0019)
1: Relates to rated current of
HD31 (alarm E0017)
Thousands: Motor type
0: Standard motor
1: Variable frequency motor
Ten thousands: Overload
protection
0: Enabled
1: Disabled
F20.01
Overload pre-alarm
detection threshold
20.0 - 200.0%
150.0%
0.1%
×
F20.02
Overload pre-alarm
detection time
0.0 - 60.0s
5.0s
0.1s
×
F20.03
Output load-loss
detection of HD31
0: Disabled. It does not detect
output load-loss
1: It detects all the time in
running process, and then
continues running after
detecting (alarm)
2: It detects only at constant
speed, and then continues
running after detecting (alarm)
3: It detects all the time in
running process, and then cut
off the output after detecting
(fault)
4: It detects only at constant
speed, and then cuts off the
output after detecting (fault)
0 1
×
F20.04
Output load-loss
detection threshold of
HD31
0 - 100%
30%
1%
×
F20.05
Output load-loss
detection time of HD31
0.00 - 20.00s
1.00s
0.01s
×
F20.06 Motor
overheat
signal
0: Does not detect
1: Positive charateristic (PTC)
2: Negative charateristic (NTC)
0 1
×
F20.07
Thermistor value at motor
overheat
0.0 - 10.0kΩ
5.0kΩ
0.1kΩ
×
F20.08
Input voltage phase loss
detection setting
0 - 50%
0: Not detect input voltage phase
loss
30% 1%
×