Appendix A Parameters
Shenzhen Hpmont Technology Co., Ltd.
―
92
―
HD31 Series User Manual V1.1
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
P02.11
T5 start time
00.00 - 23.59
00.00
0.01
×
P02.12
T5 time pressure
0.0 - P05.0 3×10 kg/cm
2
0.0
kg/cm
2
0.10kg/cm
2
×
P02.13
T6 start time
00.00 - 23.59
00.00
0.01
×
P02.14
T6 time pressure
0.0 - P05.0 3×10 kg/cm
2
0.0
kg/cm
2
0.10kg/cm
2
×
P02.15
T7 start time
00.00 - 23.59
00.00
0.01
×
P02.16
T7 time pressure
0.0 - P05.0 3×10 kg/cm
2
0.0
kg/cm
2
0.10kg/cm
2
×
P02.17
T8 start time
00.00 - 23.59
00.00
0.01
×
P02.18
T8 time pressure
0.0 - P05.0 3×10 kg/cm
2
0.0
kg/cm
2
0.10kg/cm
2
×
P02.19
T9 start time
00.00 - 23.59
00.00
0.01
×
P02.20
T9 time pressure
0.0 - P05.0 3×10 kg/cm
2
0.0
kg/cm
2
0.10kg/cm
2
×
P02.21
T10 start time
00.00 - 23.59
00.00
0.01
×
P02.22
T10 time pressure
0.0 - P05.0 3×10 kg/cm
2
0.0
kg/cm
2
0.10kg/cm
2
×
P02.23
T11 start time
00.00 - 23.59
00.00
0.01
×
P02.24
T11 time pressure
0.0 - P05.0 3×10 kg/cm
2
0.0
kg/cm
2
0.10kg/cm
2
×
P02.25
T12 start time
00.00 - 23.59
00.00
0.01
×
P02.26
T12 time pressure
0.0 - P05.0 3×10 kg/cm
2
0.0
kg/cm
2
0.10kg/cm
2
×
P02.27
Upper limit of pressure
closed-loop
0 - upper limit
50.00Hz
0.01Hz
○
P02.28
Proportional gain of
pressure closed-loop (Kp)
0.00 – 10.00
0.01
0.01
○
P02.29
Integration time of
pressure closed-loop (Ti)
0.01 - 10.00s
0.10
0.01
○
P02.30
Differential time of
pressure closed-loop (Td)
0.00 - 1.00s
0.00
0.01
○
P02.31
Sampling time (T)
0.01 - 30.00s
0.50s
0.01s
○
P02.32
Bias limit
0.0 - 20.0%
2.0%
0.1%
○
P02.33
Output wave filter of
pressure closed-loop
0.01 - 30.00s
0.50
0.01
○
P02.34
Regulating characteristic
of pressure closed-loop
0: Positive characteristi
1: Positive characteristic
0 1
○
P02.35
Digital setting for saving
selection when power
failure
0: Not saving
1:Saving
1 1
○
P03: Water Supply AIO Function Parameter, on pages 59 - 61
P03.00 AI1
function
0: Unused
1: Analoguepressure setting
2: Analoguefeedback setting
3: Anolog WL feedback
0 1
×
P03.01 AI2
function
0
1
×
P03.02 AI3
function
0
1
×
P03.03 AI4
function
0
1
×
P03.04 DI1
function
0: Unused.
1 - 7: Pump 1 - 7 commissioning
running
8 - 14: Pump 1 - 7 invalid
15, 16: Upper / Lower limit WL of
0 1
×
P03.05 DI2
function
0
1
×
P03.06 DI3
function
0
1
×
P03.07 DI4
function
0
1
×
P03.08 DI5
function
0
1
×