Shenzhen Hpmont Technology Co., Ltd.
Chapter 6 Function Introduction
HD31 Series User Manual V1.1
―
55
―
Ref. Code
Name Description
Setting Range [Default]
P00.32
Switching angle of variable and power frequecny of pump 1
-50.0 - 50.0 [0.0
°
]
P00.33
Switching angle of variable and power frequecny of pump 2
-50.0 - 50.0 0.0
°
]
P00.34
Switching angle of variable and power frequecny of pump 3
-50.0 - 50.0 [0.0
°
]
P00.35
Switching angle of variable and power frequecny of pump 4
-50.0 - 50.0 [0.0
°
]
P00.36
Switching angle of variable and power frequecny of pump 5
-50.0 - 50.0 [0.0
°
]
P00.37
Switching angle of variable and power frequecny of pump 6
-50.0 - 50.0 [0.0
°
]
P00.38
Switching angle of variable and power frequecny of pump 7
-50.0 - 50.0 [0.0
°
]
When seting as positive angle, variabe frequency phase exceeds power frequency and the difference
reaches setted angle, switching action from variable frequency to power frequcny will be started.
When setting as negative angle, variable frequency is slower than power frequency and the difference
reaches setted angle, switching action from variable frequency to power frequcny will be started.
P00.39
Dealy of pump 2 contactor breaking
0.000 - 5.000 [0.020s]
P00.40
Dealy of pump 2 contactor touching
0.000 - 5.000 [0.200s]
P00.41
Dealy of pump 3 contactor breaking
0.000 - 5.000 [0.020s]
P00.42
Dealy of pump 3 contactor touching
0.000 - 5.000 [0.200s]
P00.43
Dealy of pump 4 contactor breaking
0.000 - 5.000 [0.020s]
P00.44
Dealy of pump 4 contactor touching
0.000 - 5.000 [0.200s]
P00.45
Dealy of pump 5 contactor breaking
0.000 - 5.000 [0.020s]
P00.46
Dealy of pump 5 contactor touching
0.000 - 5.000 [0.200s]
P00.47
Dealy of pump 6 contactor breaking
0.000 - 5.000 [0.020s]
P00.48
Dealy of pump 6 contactor touching
0.000 - 5.000 [0.200s]
P00.49
Dealy of pump 7 contactor breaking
0.000 - 5.000 [0.020s]
P00.50
Dealy of pump 7 contactor touching
0.000 - 5.000 [0.200s]
For details, pleasure see P00.13, P00.14.
6