Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
―
32
―
HD31 Series User Manual V1.1
6.2.2
F01: Protection of Parameters
Ref. Code
Function Description
Setting Range [Default]
F01.00
User’s password
00000 - 65535 [00000]
XXXXX: To enable the password protection function, set any non-zero number as the password.
•
Once the password is set, to change any parameter, input correct password. Otherwise, all the
parameters cannot be changed but only read.
•
When input correct password, by pressing
key to exit to stop / run display status or by detecting
no press on the keypad within 5 minutes, the user’s password will be valid. To change parameters, input
correct password. It will restart when there is no press on the keypad within 5 minutes.
00000 : The factory setting of F01.00 is 00000, namely the password protection function is disabled.
•
If user unlocks the password, it means clearing the user’s password.
F01.01 Menu
mode
0,1 [0]
0: Full menu mode. All function parameters can be displayed.
1: Checking menu mode. Only parameters different from factory setting can be displayed.
F01.02
Function code parameter initialization (download)
0 - 6 [0]
0: No operation. HD31 is in regular parameter read / write status.
•
Whether can change the parameter depends on user’s password
status and the actual running condition of HD31.
1: Restore to factory settings.
•
Except F01.00, F01.02, F01.03, F19.19, F19.24, F20.08, F20.09, F20.21 -
F20.37, F23.00.
•
Steps:
If set F01.02 = 1, press
to ensure and the parameters are
restored to factory settings. The keypad dispalys “rESEt”. Then the
keypad will display parameters in stop status after finish restoring to
factory setting.
2: Download the keypad EEPROM parameter 1 to the current function code settings.
3: Download the keypad EEPROM parameter 2 to the current function code settings.
4: Clear fault information. The fault history of F20.21 - F20.37 will be clear.
5: Download the keypad EEPROM parameter 1 to the current function code settings (including the motor
parameters).
6: Download the keypad EEPROM parameter 2 to the current function code settings (including the motor
parameters).
F01.03
Keypad EEPROM parameter initialization (upload)
0 - 2 [0]
0: No operation. HD31 is in regular parameter read / write status.
1: Upload the current function code settings to the keypad EEPROM
parameter 1.
2: Upload the current function code settings to the keypad EEPROM
parameter 2.
Note: F01.00, F01.02, F01.03, F20.21 - F20.37 and Group y do not upload or
download
F01.02 = 2 / 3 / 5 / 6
HD31
Keypad
Download
Keypad stored
function parameter
F01.03 = 1/2
HD31
Keypad
Upload
HD31 present setting
function parameter