Shenzhen Hpmont Technology Co., Ltd.
Chapter 6 Function Introduction
HD31 Series User Manual V1.1
―
31
―
Ref. Code
Function Description
Setting Range [Default]
F00.15
Jog running frequency digital setting 1
0 - upper limit frequency
[5.00Hz]
F00.16
Interval of jog running
0.0 - 100.0 [0.0s]
After cancel the jog command, HD31 will not
respond to the jog command at the interval of jog
running set by F00.16.
•
After the interval of jog is completed, it
immediately executes the arrived jog
command. As show in figure.
F00.17 Running
direction
0,1 [0]
0: The same as running command.
1: Opposite to running command.
F00.18 Reverse
0,1 [0]
This function is valid when F00.11 = 0,1,2.
0: Permitted.
1: Prohibitted. It can respond to the FWD / REV commands. When the analogue value is set to positive /
negative voltage and the negative voltage corresponds to the reverse frequency, HD31 will run in
accordance with the zero-frequency run.
F00.19
Dead time of direction switch
0.0 - 3600.0 [0.0s]
Defines the dead time of direction switch, namely, the time of
zero-frequency output in the process of direction switch shown as
the right figure.
F00.20
Key enable of optional keypad
0,1 [0]
0: Enabled. When HD31 connects to two keypads, the keys of optional display using the communication
port can be operated.
1: Invalid. When HD31 connects to two keypads, the keys of optional display using the communication port
can not be operated.
F00.21 Dormant
function
0,1 [0]
0: Disabled. This function is invalid.
1: Enabled. At running status, when the setting frequency ≤ lower limit of running frequency (F00.09), HD31
coasts to stop and enters dormant status.
F00.22
Dormancy wake up time
0.0 - 360.0 [0.0s]
When HD31 is at dormancy status, and the setting frequency > lower limit of running frequency (F00.09),
and the duration achieves the setting time of F00.22, then HD31 wakes up from dormancy status, and starts
at the mode of F02.00.
F00.16
Jog running
frequency
Time
Time
Jog command
Acc
Dec
Frequency
F00.19
FWD
REV
0
Time
Frequency
6