Shenzhen Hpmont Technology Co., Ltd.
Chapter 3 Machenical Installation
HD31 Series User Manual V1.1
―
9
―
Chapter 3
Machenical Installation
3.1
Precautions
•
Do not install if HD31 is incomplete or impaired.
•
When conveying HD31, please employ suitable tools according to its weight. Avoid scratch to the product. Be
careful: rollover and drop may cause hurt.
•
Make sure that HD31 is far from explosive and flammable things.
•
Do not do wiring operation until power supply is cut off for more than 10 minutes, the internal charge indicator of
HD31 is off and the voltage between (+) and (-) of the main circuit terminals is below 36V.
•
It is required not only carry the keypad and the cover but also bottom enclosure of HD31.
•
Do not let wires, screws or residues fall into HD31 when installing.
3.2
Installation Site Requirement
Ensure the installation site meets the following requirements:
•
Do not install at direct sunlight, moisture, water droplet location;
•
Do not install at flammable, explosive, corrosive gas and liquid location;
•
Do not install at oily dust, fiber and metal powder location;
•
Be vertical installed on fire-retardant material with a strong support;
•
Make sure adequate cooling space for HD31 so as to keep ambient temperature between
- 10 - + 40
℃
;
•
Install at where the vibration is 3.5m/s
2
in 2 - 9Hz, 10m/s
2
in 9 - 200Hz (IEC60721-3-3);
•
Install at where the humidity is less than 95%RH and non-condensing location;
•
Protection level of HD31 is IP20 and pollution level is 2 (Dry, non-conducting dust pollution).
Note:
1. It needs derating use if running temperature exceeds 40
℃
. The derating value of the output current of
HD31 shall be 2% for each degree centigrade. Max. allowed temperature is 50
℃
.
2. Keep ambient temperature between -10 - +40
℃
. It can improve the running performance if install at
location with good ventilation or cooling devices.
Danger
Warning
3