Chapter 6 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
―
26
―
HD31 Series User Manual V1.1
6.1
Group d: Display Parameters
Users can directly check the status parameters by checking the function code of Group d.
6.1.1
d00: Status Display Parameters
Ref. Code
Function Description
Setting Range [Default]
d00.00 Inverter
series
[Actual value]
d00.01
Software version of the control board
[Actual value]
d00.03
Special software version of the control board
[Actual value]
d00.05
Software version of the keypad
[Actual value]
d00.06
Customized series No.
[Actual value]
d00.08
Rated current of the inverter
[Actual value]
d00.09
Extended function of the inverter
[Actual value]
Display extended function of HD31.
0: No extended function.
1: Constant pressure water supply function.
d00.10 Inverter
status
[Actual value]
Display HD31 status, as shown in the following table:
Bit15: Unused
Bit14: Unused
Bit13: Current limit
0: Invalid
1: Valid
Bit12: Stall overvoltage
0: Invalid
1: Valid
Bit11: Unused
Bit10: Speed limit value
0: Invalid
1: Valid
Bit9: Unused
Bit8: Auto-tuning
0: Not in auto-tuning
1: In auto-tuning
Bit7: DC braking
0: Invalid
1: Valid
Bit6: Unused
Bit5&Bit4: Acc / Dec / Constant
00: Constant
11: Constant
01: Acc
10: Dec
Bit3: Zero speed
running
0: Invalid
1: Valid
Bit2: Forward / reverse
0: Forward
1: Reverse
Bit1: Run / stop
0: Stop
1: Run
Bit0: Inverter fault
0: No fault
1: Fault
123
d00.14
Setting frequency
[Actual value]
d00.15
Setting frequency (after Acc / Dec)
[Actual value]
d00.16
Output frequency
[Actual value]
d00.17 Setting
RPM
[Actual value]
d00.18 Running
RPM
[Actual value]
d00.19
Three-phase power supply input sequence phase
[Actual value]
Display sequence phase of the three-phase input.
•
0: Positive sequence: L1 (R) preceding L2 (S) preceding L3 (T).
•
1: Negative sequence: L1 (R) preceding L3 (T) preceding L2 (S).
d00.20 Output
voltage
[Actual value]
d00.21 Output
current
[Actual value]
d00.23 Output
torque
[Actual value]
Display output torque which is the relative percentage of the motor rated torque.
d00.24 Output
power
[Actual value]
Display present actual output power whose unit is 0.1kW.