Appendix A Parameters
HD31 Series User Manual V1.1
―
75
―
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
RLY1 - RLY10
0: Output terminals disconnect
with common terminals
1: Output terminals connect
with common terminals
d00.55
Total time at power-on
0 - 65535h
*
d00.56
Total time at running
0 - 65535h
*
d00.57
High bit of motor total
energy consumption
0 - 65535k kW.h
*
d00.58
Low bit of motor total
energy consumption
0.0 - 999.9kW.h
*
d00.59
High bit of energy
consumption at this time
running
0 - 65535k kW.h
*
d00.60
Low bit of energy
consumption at this time
running
0.0 - 999.9kW.h
*
d00.61 Present
fault
0 - 100
100: means undervoltage
*
F00: Basic Parameters, on pages 29 - 32
F00.01 Motor
control
mode
0: V/f control
1: Unused
2: SVC control
0 1
×
F00.02
Inverter type setting
0: G type
1: P type
1 1
×
F00.04 Extension
card
selection
0: Invalid
2: HD30-WIO extension valid
2 1
×
F00.05
HD31 extended function
0: No extended
1: Constant pressure water
supply
0 1
×
F00.06
Max. output frequency of
HD31
50.00 - 400.00Hz
50.00Hz
0.01Hz
×
F00.07
Upper limit of running
frequency setting source
0: Digital setting (F00.08)
1: Analogue input setting
2: DI6 pulse setting
0 1
×
F00.08
Upper limit of running
frequency
0.00 - F00.06
50.00Hz
0.01Hz
×
F00.09
Lower limit of running
frequency
0.00 - upper limit
0.00Hz
0.01Hz
×
F00.10
Frequency setting sources
0: Keypad setting
1: Terminal digital setting
2: SCI communication setting
3: Analogue setting
4: DI6 pulse setting
0 1
×
F00.11
Command setting source
0: Keypad setting
1: Terminal setting
0 1
×