Appendix A Parameters
Shenzhen Hpmont Technology Co., Ltd.
―
80
―
HD31 Series User Manual V1.1
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
mode of motor
component
1: Depend on torque current
component
F09.16
Oscillation-suppression
coefficient of motor
0 - 200
50
1
○
F15: Digital I/O Terminal Parameters, on pages 38 - 41
F15.00 DI1
function
0: Unused
1: Inverter enabled
2, 3: FWD / REV
4: Three-wire running mode
12: External stop command
input
41, 42: Coast to stop normally
open / normally closed input
44, 45: External fault normally
open / normally closed input
46: External reset (RST) input
53: Pulse frequency input (DI6)
54: Clear fault records
2 1
×
F15.01 DI2
function
3
1
×
F15.02 DI3
function
0
1
×
F15.03 DI4
function
0
1
×
F15.04 DI5
function
0
1
×
F15.05 DI6
function
0
1
×
F15.06 DI7
function
0
1
×
F15.07 DI8
function
0
1
×
F15.08 DI9
function
0
1
×
F15.15
Terminal input positive
and negative logic setting
Bit0 - Bit8 is corresponding to
DI1 - DI9
0: Positive logic
1: Negative logic
000 1
○
F15.16
FWD / REV running mode
0: Two-wire running mode 1
1: Two-wire running mode 2
2: Three-wire running mode 1
3: Three-wire running mode 2
0 1
×
F15.18 DO1
function
0: Unused
1: Inverter is ready
2: Inverter running
3: Forward running
4: Reverse running
6:Zero-frequency status
7: Zero-frequency running
31: Inverter fault
32: External fault
35: Dormancy indicating
function
38: High-frequency output
(DO2)
2 1
×
F15.19 DO2
function
0
1
×
F15.20 RLY1
function
31
1
×
F15.21 RLY2
function
0
1
×
F15.22 RLY3
function
0
1
×
F15.23
RLY4
function
0
1
×
F15.24
Output terminal logic
setting
Bit0 - Bit1 is corresponding to
DO1 - DO2
Bit2 - Bit11 is corresponding to
RLY1 - RLY10
0: Positive logic
1: Negative logic
000 1
○
F15.28
Zero-frequency signal
0.00 - upper limit
0.00Hz
0.01Hz
○