Shenzhen Hpmont Technology Co., Ltd.
Chapter 6 Function Introduction
HD31 Series User Manual V1.1
―
39
―
Ref. Code
Name Description
Setting Range [Default]
F15.16
FWD / REV running mode
0 - 3 [0]
•
FWD:DI terminal is defined as No. 2 function.
•
REV: DI terminal is defined as No. 3 function.
•
Three-wire running: DI terminal is defined as No. 4 function.
0, 1: Two-wire running mode 1, 2.
•
When stop command coming from other sources makes HD31stop though the terminal logic enabled
in the terminal control mode, there is no running command even the control terminals FWD / REV are
still valid.
•
To run HD31 again, trigger the active FWD and REV.
2: Three-wire running mode 1.
•
If the shift between SB2 and SB3 is disabled, HD31 will keep the control mode.
3: Three-wire running mode 2.
•
If SB2 changes from enabled into disabled, HD31 will keep the same mode.
F15.18 DO1
function
0 - 35 [2]
F15.19 DO2
function
0 - 38 [0]
F15.20 RLY1
function
0 - 35 [31]
F15.21 RLY2
function
0 - 35 [0]
F15.22 RLY3
function
0 - 35 [0]
F15.23 RLY4
function
0 - 35 [0]
0:
Unused.
1: Inverter is ready.
•
HD31 completes power on and no fault occurs, then it can normally run the indicating signal.
2: Inverter running.
•
HD31 is in run status and outputs indicating signal.
3: Forward running.
•
HD31 is forward running the indicating signal.
4: Reverse running.
•
HD31 is reverse running the indicating signal.
Stop
Reverse
Forward
Stop
Stop
Reverse
Forward
Stop
0
0
0
1
1
1
1
0
Run Command
K2
K1
K1
FWD
REV
K2
P24
SEL
DIx
DIy
COM
F15.16=1
F15.16=0
COM
F15.16=2
F15.16=3
P24
SEL
DIx
DIz
DIy
COM
P24
SEL
DIx
DIz
DIy
SB2
SB2
SB3
K
SB1
SB1
FWD
FWD / REV
RUN
REV
SB1: Normally closed stop button
SB2: Normally open forward button
SB3: Normally open reverse button
K: Direction selection terminal (level on)
K = 0(forward) K = 1(reverse)
SB1: Normally closed stop button
SB2: Normally open run button
Three-wire
Three-wire
6