Control the start/stop via terminals and set the running frequency via display panel
1. The terminal DI1 is forward running signal input, and DI2 is reverse running signal input, their
wirings are as following figure.
2. After power on, set the functional parameters in accordance with wirings, as following table.
No.
Parameter name
Setting value
Meaning
F00.10
Frequency setting source
selection
3
Analogue setting
F00.11
Command setting source
selection
1
Terminal running command source
F15.00
DI1 terminal function
selection
2 (factory setting)
Forward running function (terminal
forward signal input)
F15.01
DI2 terminal function
selection
3 (factory setting)
Rervese running function (terminal
rervese signal input)
F16.01
Analogue input AI1
function selection
0
Reserved
F16.00
Display panel with
potentiometer function
selection
2
Frequency setting source
(via
potentiometer of display panel)
Note:
Function parameters F16.00
-
F16.02 cannot be the same. If you want to set F16.00 as 2,
you should set F16.01 (factory value is 2) as other value (except 2) firstly.
3. Set motor parameters (see motor nameplate parameters) and acceleration/deceleration time
via the display panel, as following table.
No.
Parameter name
No.
Parameter name
F08.00
Rated power of motor 1
F08.04
Rated RPM of motor 1
F08.01
Rated voltage of motor 1
F08.02
Rated current of motor 1
F03.01
Acceleration time 1
F08.03
Rated frequency of motor 1
F03.02
Deceleration time 1
4. By rotating the potentiometer of display panel to set the running frequency.
5. Close the K1 of the wiring diagram, the motor will run forward; close K2, run reverse;
simultaneously close or disconnect, the motor will stop.
DI1
COM
K1
K2
Forward terminal
DI2
Reverse terminal
DO1
R1A
R1C
R1B
Fault indication normally closed contact
Output indicating signal at running
Fault indication normally open contact
Common terminal