Shenzhen Hpmont Technology Co., Ltd
Appendix A Parameters
HD20 Series Inverters User Manual
-
121
-
No.
Name
Range
Factory
Default
Unit
Modified
attributes
Setting
1: Reserved
2: Vector control without PG
F00.02 Reserved
F00.03 Motor selection
0: Motor 1
1: Motor 2
0
1
×
F00.04 Reserved
F00.05 Reserved
F00.06
Inverter max. output
frequency
50.00
-
400.00Hz
50.00Hz
0.01Hz
×
F00.07
Upper limit of operation
frequency setting source
0: Digital setting (F00.08)
1: Analogue input setting
2: Terminal pulse setting
0
1
×
F00.08
Upper limit of operation
frequency
0.00
-
F00.06
50.00Hz
0.01Hz
×
F00.09
Lower limit of operation
frequency
0.00
-
upper limit
0.00Hz
0.01Hz
×
F00.10
Frequency setting sources
selection
0: Display panel digital setting
1: Terminal digital setting
2: SCI communication setting
3: Analogue setting
4: Terminal pulse setting
0
1
×
F00.11
Command setting source
selection
0: Display panel running
source
1: Terminal running source
2: SCI communication running
source
0
1
×
F00.12
Function selection of the
multi-function key
0: Switch the display panel
running direction
1: Switch local and remote
control
0
1
○
F00.13
Starting frequency digital
setting
0.00
-
upper limit
50.00Hz
0.01Hz
○
F00.14
UP/DOWN digital setting
control
Units: Frequency setting save
selection at power outage
0: Frequency setting will not be
saved at power outage
1: Frequency setting will be
saved to F00.13 at power
outage
Tens: Frequency setting
control selection at stop
0: Frequency setting will not be
restored to F00.13 at stop
1: Frequency setting will be
restored to F00.13 at stop
1001
1
×
A