Appendix A Parameters
Shenzhen Hpmont Technology Co., Ltd
―
146
―
HD20 Series Inverters User Manual
No.
Name
Range
Factory
Default
Unit
Modified
attributes
Setting
F19.22
Deceleration time at auto
current limiting
0.00
-
600.00s
0.00: Limited the current
without deceleration
10.00s
0.01s
×
F19.23
Enabled mode of terminal
run command
0: Rise edge enabled mode
1: Level enabled mode
0
1
○
F19.24
Action voltage of braking
unit
220V: 380
-
450V
380V: 630
-
750V
Dependent
on inverter
model
1V
×
F19.25 Reserved
F19.26 Preset length
0
-
65535m
0m
1m
×
F19.27 Actual length
0
-
65535m
0m
1m
*
F19.28 Length ratio
0.001
-
30.000
1.000
0.001
×
F19.29
Length checking
coefficient
0.001
-
1.000
1.000
0.001
×
F19.30 Measuring shaft diameter
1.00
-
100.00cm
10.00cm
0.01cm
×
F19.31
Number of pulses per
revolution
1
-
9999
1
1
×
F19.32
Length arrive and output
function selection
0: Output level signal
1: Output 500ms pulse
0
1
○
F19.33
Record of length disposal
after length arrive
0: Auto-clear
1: No change
0
1
○
F19.34
Record of length disposal
at stop
0: Auto-clear
1: No change
0
1
○
F19.35 Reserved
F19.36 Reserved
F19.37 Reserved
F19.38 Reserved
Group F20 Protection of Fault Parameters (refer to pages 101
F20.00
Overload pre-alarm
detection
Units: Overload pre-alarm
detection
0: It is active all the time in
running status
1: It is active only at constant
speed
Tens: Action selection for
overload pre-alarm
0: The inverter doesn’t alarm
and continues operation when
detecting an active overload
signal
1: The inverter alarms and
stops operation when
detecting an active overload
signal
00000
1
×