Shenzhen Hpmont Technology Co., Ltd
Appendix A Parameters
HD20 Series Inverters User Manual
-
145
-
No.
Name
Range
Factory
Default
Unit
Modified
attributes
Setting
frequency
F19.06
Adjustment coefficient of
setting frequency
0.0
-
200.0%
100.0%
0.1%
○
F19.07
Control selection of
cooling fan
0: Auto stop mode
1: Immediate stop mode
2: The fan runs continuously
when power on
0
1
○
F19.08
Cooling fan controls
delaying time
0.0
-
600.0s
30.0s
0.1s
○
F19.09 Droop control
0.00
-
10.00Hz
0.00Hz
0.01Hz
×
F19.10 Zero-frequency threshold
0.00
-
F00.06
1.00 Hz
0.01Hz
○
F19.11
Action selection at setting
frequency is lower than
zero-frequency threshold
0: Run according to frequency
command
1: Holding stop, no output
2: Run according to
zero-frequency threshold
3: Run according to
zero-frequency
0
1
×
F19.12
Trip-free selection at
momentary power loss
0: This function is disabled
1: This function is enabled
0
1
×
F19.13
Deceleration time at
voltage compensation
0.01
-
600.00s
5.00s
0.01s
○
F19.14
Voltage rise diagnosis time
of trip-free operation at
momentary power loss
0.00
-
10.00s
0.10s
0.01s
○
F19.15
Reference voltage of
trip-free operation at
momentary power loss
0
-
999V
Dependent
on inverter
model
1V
×
F19.16 Restart after power failure
0: This function is disabled
1: This function is enabled
0
1
×
F19.17
Delay time for restart after
power failure
0.00
-
10.00s
2.00s
0.01s
○
F19.18
Protection of stall
overvoltage
0: Disabled (with braking
resistance)
1: Enabled
1
1
×
F19.19 Stall overvoltage point
0
-
999V
700V
1V
×
F19.20
Auto current limiting
selection
0: Disabled
1: Enabled in Acc./Dec.
running process, but disabled
in constant speed runnng
process
2: Enabled both in Acc./Dec.
and in constant speed running
proces
0
1
×
F19.21
Auto current limiting
threshold
20.0
-
200.0%
150.0%
0.1%
×
A