Figure 122 Management port IP address conflict blink pattern
Using the CLI or GUI, the IP address conflict blink pattern may be cleared using the
Beacon OFF
function.
Over-temperature blink pattern
An over-temperature condition is indicated by a five-blink pattern followed by a two-second pause.
The five-blink pattern indicates that the air temperature inside the MPX200 has exceeded the failure
temperature threshold of 70 °C (
Figure 123 (page 143)
).
Figure 123 Over-temperature blink pattern
If the Heartbeat LED shows the over-temperature blink pattern, do the following:
1.
Inspect the chassis air vents. Are the intake and exhaust vents clear?
•
If yes, proceed to the next step.
•
If not, remove any debris from the fan intake and exhaust. If the condition persists, proceed
to the next step.
2.
Consider the ambient air temperature near the MPX200 and the clearance around the MPX200.
Make the necessary corrections.
3.
If the condition persists, power down the MPX200. Contact your authorized maintenance
provider.
MPX200 chassis diagnostics
143