Troubleshooting 88
Battery Test did not run
Possible Cause:
The UPS is On Battery.
Action:
The UPS must be in a certain state before the battery test runs. For more information, refer to the
section, "Parameters menu option ("
Parameters menu
" on page
51
)."
Browser does not display the web interface for an
installed management module
Action:
1.
Be sure that the IP address and port number are correct. The default port number for non-secure
browser connection is port 80. The default port number for secure SSL browser connection is 443.
2.
Be sure that the web interface (HTTP/HTTPS) is enabled on the management module.
Browser incorrectly displays English or Japanese
characters
Possible Cause:
Another user with different language settings logs in to the web interface.
Action:
Log out of the web interface, close the browser window, and then sign in to the web interface
again.