If communication is established, the target indicator will show the mode of the controller
Target: yy(R) as shown in the status section above in this chapter, section Cscape Status Bar.
Local ID and Target ID Match
If the controller is not communicating, you may need to set the Target ID of the controller in
Cscape or change the controllers ID on the unit itself. The Target ID allows directing
communications to a particular unit when multiple units are connected via a CsCAN network.
Units without CsCAN network ports respond to any network ID and do not require the ID to be
configured.
To check or change the ID on the XL+ OCS, press the System Menu key.
The first item in the menu is Set Networks. Pressing Enter allows the ID of the unit to be
viewed or modified.
To point Cscape at the correct controller, change the Target ID of Cscape use the Controller
→
Set Target Network ID dialog.
When connected directly to the controller to which Cscape
communications are required, the
Local ID and the Target
ID should match.