MAN1106-07-EN_XL+_UserManual
M a y 6
t h
, 2 0 2 0
P a g e 33 | 192
5.5 View Diags
The View Diags Sub-Menu displays up to 11 System Diagnostics, none of which are editable.
The first two System Diagnostics are critical. If either of these indicate a Fault condition, the
XL+ OCS will not enter or remain in Run mode, and the problem must be investigated and
corrected.
Logic Error:
Ok = All executed ladder instructions are legal for loaded firmware
Fault = A ladder instruction not supported by firmware was found
User Program:
Ok = Ladder program and I/O configuration loaded successfully
Fault = Ladder program or I/O configuration not loaded or load failed
The last nine System Diagnostics are informational. If any of these indicate a warning condition,
the XL+ OCS can still enter and remain in Run mode, but the problem should be investigated
and corrected.
User Graphics
Ok = Application graphics objects loaded successfully.
Fault = Application graphics objects not loaded or load failed.
W-Dog Trips
0 = Watchdog timer has not tripped since the last power-up.
x = Number of times watchdog timer has tripped.
Net Errors
0 = No CAN network bus-off errors have occurred.
x = Number of CAN network bus-off errors that have occurred.
Network State
Ok = At least one other node was found on the CAN network.
Warning = No other nodes were found on the CAN network.
Network ID
Ok
= This node’s CAN Network ID is in the range 1 to 253.
Warning
= This node’s CAN Network ID was out of range at power
-up.
Dup Net ID
Ok
= This node’s Network ID is unique on the CAN
network.
Warning
= This node’s Network ID is duplicated in another node.
Clock Error
Ok = Time and date have been set.
Warning = Time and date need to be set.
I/O System
Ok = I/O configuration matches the installed I/O and COM modules.
Warning = I/O configuration needs updating to match installed modules.
Battery
Ok = Backup battery operating properly.
Warning = Backup battery needs to be replaced.