3.6.4.5.5 Special Configuration
If used, the correct settings are described in the additional system manual of the customer-
specific device.
Otherwise for S1-S8 the DEFAULT-setting (all checkboxes disabled) should not be changed
due to compatibility reasons.
3.6.4.5.6 String Output
The string output for the transmission must be selected here:
•
hopf
Binäry String
•
hopf
time Universal
•
hopf
Master/Slave-String
•
hopf
Standard String (6021)
•
Trimble Time String (TSIP)
•
SINEC H1 Extended
•
SAT 1703 Time String
•
ABB Melody (CR/LF)
•
ABB Melody (LF/CR)
•
hopf
6021 String 2000
•
IEC-103 (ASDU Type 6)
3.6.4.5.6.1
hopf
Binary String
The
hopf
Binary String can be used to synchronize slave systems with the time data of the
master system.
Required:
•
Transmision Time every second
•
With second forerun / control character every second
•
9600 baud, 8 bit, 1 stop bit, no parity
Example:
(STX):TIME:80;0233D88F08;07E0;003C;F4108014*6B(CR)(LF) (ETX)
3.6.4.5.6.2
hopf
time Universal
The
hopf
time Universal String can be used to synchronize slave systems with the time data
of the master system.
Required:
•
Transmision Time every second
•
With second forerun / control character every second
•
UTC time
•
9600 baud, 8 bit, 1 stop bit, no parity
Example:
(STX)731144501900000FFFF*23(CR)(LF) (ETX)