XNX Universal Transmitter
Section 3 - Calibration
100
3.4 Calibrate mA Output
Use Calibrate mA Output to adjust the milliamp output to provide
the correct output levels at peripheral devices connected to the
transmitter�
Figure 219. Calibrate mA Output Menu
To adjust the 4mA output, use the switches to increase or
decrease the output, then use
✓
to accept the new value and
move to the 20mA setting or
✖
to discard the selection and
return to the previous menu�
Figure 220. Calibrate mA Output Screens
During installation, an mA meter must be connected in series
with the 4-20 mA loop as shown below�
Control Equipment
XNX
mA
Meter
4-20 mA loop
4-20 mA loop
Remote end
R load
Figure 221. 4-20 mA loop with mA meter
Note:
Calibrated mA output is required for proper operation of internal
diagnostics.
An F165 fault will be reported if the 4-20 mA calibration fails�
3.5 Align Excel (Searchline Excel)
Figure 222. Align Excel Menu
For detailed information on Aligning the Searchline Excel, see the
Searchline Excel Technical Manual (P/N: H-MAN0530-V1)�
Alignment Bargraph
Signal Strength
1.00 Signal Strength Target
Reference Value
Figure 223. Align Excel Screen
Align the unit using the information found in the Searchline Excel
manual� As the alignment is performed, the transmitter display will
indicate the signal strength in the form of a bar graph� Align the
Excel until the signal strength bar graph reaches or exceeds 1�00 as
shown on the display�
Summary of Contents for XNX
Page 1: ...Technical Manual XNXTM Universal Transmitter ...
Page 2: ......
Page 6: ...XNX Universal Transmitter Table of Contents 4 Table of Contents ...
Page 11: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 9 1 Introduction ...
Page 91: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 89 3 Calibration ...
Page 104: ...XNX Universal Transmitter Section 3 Calibration 102 ...
Page 105: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 103 4 Maintenance ...
Page 128: ...XNX Universal Transmitter Section 5 Warnings Faults 126 ...
Page 129: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 127 6 Specifications ...
Page 152: ...XNX Universal Transmitter Section 6 Specifications 150 Figure 232 XNX BT Configuration ...
Page 161: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 159 7 Control Drawings ...
Page 162: ...XNX Universal Transmitter Section 7 Control Drawings 160 7 1 XNX UL INMETRO ...
Page 163: ...XNX Universal Transmitter Section 7 Control Drawings 161 ...
Page 164: ...XNX Universal Transmitter Section 7 Control Drawings 162 ...
Page 165: ...XNX Universal Transmitter Section 7 Control Drawings 163 7 2 XNX UL CSA FM ...
Page 166: ...XNX Universal Transmitter Section 7 Control Drawings 164 ...
Page 167: ...XNX Universal Transmitter Section 7 Control Drawings 165 ...
Page 192: ...XNX Universal Transmitter Appendix B Modbus Protocol 190 ...
Page 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Appendix C Warranty ...
Page 195: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 193 Index ...
Page 199: ......