XNX Universal Transmitter
Section 2 - Installation and Operation
71
Searchline (see the table in the next column)�
Figure 102. mA Levels Menu
Using the switches, move to the mA output to be changed
and use
✓
to select it�
✓
Figure 103. Set mA Levels for Warning
Use the switches to decrement or increment the value until
the desired value appears� Use
✓
to select the value and move
to the next setting� Repeat for each setting to be changed�
The default values and available output ranges for Inhibit,
Warning, Overrange, Beam Blocked, and Low Signal are shown
in the following table� See
Section
5 Warnings/Faults
for more
information�
Signal
Output (mA)
Default
Min
Max
I
Inhibit
2.0
1.0
3.5
W
Warning
3.0
1.0
3.5
O
Overrange
21.0
20
22
B
Beam Blocked
1.0
1.0
4.0
L
Low Signal
1.0
1.0
4.0
Figure 104. Set mA Levels for Inhibit
After all changes have been made, use the switches to
move to the ‘
ü
’ and use
✓
on the front panel to accept and save
the settings� If
‘
ü
’ is not selected, none of the changes will be
saved�
Figure 105. mA Settings Saved
Calibration Interval
Calibration Interval allows a desired interval for sensor
calibration to be set for sensors attached to the transmitter� The
transmitter will generate a warning when the interval is reached�
Figure 106. Calibration Interval Menu
Calibration Interval will not appear when an IR personality board
is attached and the mA sensor type is set as ‘Other mA Sensor’�
The default calibration values for the “Calibration Required”
diagnostic vary based on sensor type� This value can be repro-
grammed in accordance with site requirements to ensure the
highest level of safety� Correct operation of each sensor should
be confirmed using calibration with a certified gas of known con-
centration before commissioning�
Although the calibration Interval can be set to any value be-
tween 0 and 360 days, Honeywell Analytics recommends that the
interval for electrochemical and catalytic sensors be set to 180
Summary of Contents for XNX
Page 1: ...Technical Manual XNXTM Universal Transmitter ...
Page 2: ......
Page 6: ...XNX Universal Transmitter Table of Contents 4 Table of Contents ...
Page 11: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 9 1 Introduction ...
Page 91: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 89 3 Calibration ...
Page 104: ...XNX Universal Transmitter Section 3 Calibration 102 ...
Page 105: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 103 4 Maintenance ...
Page 128: ...XNX Universal Transmitter Section 5 Warnings Faults 126 ...
Page 129: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 127 6 Specifications ...
Page 152: ...XNX Universal Transmitter Section 6 Specifications 150 Figure 232 XNX BT Configuration ...
Page 161: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 159 7 Control Drawings ...
Page 162: ...XNX Universal Transmitter Section 7 Control Drawings 160 7 1 XNX UL INMETRO ...
Page 163: ...XNX Universal Transmitter Section 7 Control Drawings 161 ...
Page 164: ...XNX Universal Transmitter Section 7 Control Drawings 162 ...
Page 165: ...XNX Universal Transmitter Section 7 Control Drawings 163 7 2 XNX UL CSA FM ...
Page 166: ...XNX Universal Transmitter Section 7 Control Drawings 164 ...
Page 167: ...XNX Universal Transmitter Section 7 Control Drawings 165 ...
Page 192: ...XNX Universal Transmitter Appendix B Modbus Protocol 190 ...
Page 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Appendix C Warranty ...
Page 195: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 193 Index ...
Page 199: ......