XNX Universal Transmitter
Section 2 - Installation and Operation
56
Note:
Calibration of sensors attached to the transmitter is mandatory
before the sensor can be used for gas monitoring. Refer to
Section
3 - Calibration
for the procedure.
Note:
For initial commissioning, refer to EN 60079-29-2.
2.4.2 LCD and LED Test
The LCD and LED test is performed in the initialization after
powering on� All LCD pixels and LEDs (red, green, and yellow)
are turned on for 1�5 seconds� The LCD then goes blank and the
LEDs turn off�
2.4.3 XNX IR Units Configured for
Searchline Excel
When powering the transmitter fitted with a Searchline Excel
sensor, the following procedure must be followed to assure
proper installation�
1� Verify that the transmitter is wired correctly according to
this manual and the associated control equipment manual�
2� Apply power to the XNX transmitter� This will in turn
provide power to the sensor�
3� The sensor output will be forced to 2mA (default fault/
inhibit)�
4� The XNX transmitter will enter a boot-up routine, displaying
the initialization screen� The transmitter will load its
operating system, data from the sensor, sensor software
version numbers, gas type, the detection range and span
calibration gas level, estimated time to next calibration
due, and self test result� This will take about 45 seconds�
Figure 63. XNX Initialization and General Status Screens
In the final stages of boot-up, warnings and faults
may be observed until the user performs the proper
configuration, calibration, and reset activities
described in the following sections� See
Section 5
for
descriptions of warnings and faults�
5� When the XNX completes boot-up, perform a soft reset
(see
Section 3�6 Soft Reset)
on the Excel sensor from the
Calibration Menu� When the soft reset is intitated, the RS-
485 communication will be temporarily interrupted and
faults F120 and/or F161 may be observed� The RS-485
communication will be re-established in a few minutes and
the faults will automatically be reset in the Non-Latching
mode� F120 and/or F161 must be reset manually in the
Latching mode�
6� Set the
Path Length
for the application, then align the
transmitter and receiver (see
Section 3�5 Align Excel
)�
7� Once the alignment is complete, a Zero Calibration
must be performed on the Excel sensor to complete
the commissioning process� (See the Searchline Excel
Summary of Contents for XNX
Page 1: ...Technical Manual XNXTM Universal Transmitter ...
Page 2: ......
Page 6: ...XNX Universal Transmitter Table of Contents 4 Table of Contents ...
Page 11: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 9 1 Introduction ...
Page 91: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 89 3 Calibration ...
Page 104: ...XNX Universal Transmitter Section 3 Calibration 102 ...
Page 105: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 103 4 Maintenance ...
Page 128: ...XNX Universal Transmitter Section 5 Warnings Faults 126 ...
Page 129: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 127 6 Specifications ...
Page 152: ...XNX Universal Transmitter Section 6 Specifications 150 Figure 232 XNX BT Configuration ...
Page 161: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 159 7 Control Drawings ...
Page 162: ...XNX Universal Transmitter Section 7 Control Drawings 160 7 1 XNX UL INMETRO ...
Page 163: ...XNX Universal Transmitter Section 7 Control Drawings 161 ...
Page 164: ...XNX Universal Transmitter Section 7 Control Drawings 162 ...
Page 165: ...XNX Universal Transmitter Section 7 Control Drawings 163 7 2 XNX UL CSA FM ...
Page 166: ...XNX Universal Transmitter Section 7 Control Drawings 164 ...
Page 167: ...XNX Universal Transmitter Section 7 Control Drawings 165 ...
Page 192: ...XNX Universal Transmitter Appendix B Modbus Protocol 190 ...
Page 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Appendix C Warranty ...
Page 195: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 193 Index ...
Page 199: ......