XNX Universal Transmitter
Section 5 - Warnings/Faults
116
Fault
Description
Appli-
cable
Sensors
Latching / Non-
Latching
Frequency of
Diagnostic
Event History Data
Action For Resolution
F126
Sensor Path Ob-
scured
Optima
Non-latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Sensor fault or warn-
ing code (Note 4)
Check location for external interference� Check sensor for dirty windows�
F127
Beam Block
Excel
Non-latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Sensor fault or warn-
ing code (Note 4)
Check location for external interference or obstructions in the IR path�
Check sensor for dirty windows� Check Excel alignment�
F128
Sensor Installation
Not Complete
Excel
Non-latching
XNX polls sensor
every 2 seconds,
diagnostic fre-
quency controlled
by sensor
Sensor fault or warn-
ing code (Note 4)
Check Excel alignment� Perform a zero calibration�
F130
Option Communi-
cation Failure
All
Non-latching
2 seconds
Option module ID:
0=None, 1=Foun-
dation
TM
Fieldbus,
2=Modbus
®
, 3=Relay
Check that installed option matches the option indicated in the XNX part
number� If the option has been changed, the new option must be set up
in Information->Transmitter Data as described in the manual�
F133
Not used
F143
Stabilization
Timeout
All
Latching
2 seconds
Warm up time (sec-
onds x100)
Cycle power, contact Honeywell Analytics’ Service Department if prob-
lem persists�
F145
Reflex Failure
ECC
Non-latching
Dependent on
sensor, typically 8
hours; Once fault
is detected: every
15 minutes
nA/mV
ECC sensor is no longer functioning properly� Replace sensor�
F146
Unknown Sensor
Failure
Optima,
Excel
Non-latching
2 seconds
Sensor fault or warn-
ing code (Note 4)
Contact Honeywell Analytics’ Service Department�
F148
Internal option
board hardware
failure
All
Non-latching
2 seconds
Option board error
status (Note 6)
Contact Honeywell Analytics’ Service Department�
Summary of Contents for XNX
Page 1: ...Technical Manual XNXTM Universal Transmitter ...
Page 2: ......
Page 6: ...XNX Universal Transmitter Table of Contents 4 Table of Contents ...
Page 11: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 9 1 Introduction ...
Page 91: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 89 3 Calibration ...
Page 104: ...XNX Universal Transmitter Section 3 Calibration 102 ...
Page 105: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 103 4 Maintenance ...
Page 128: ...XNX Universal Transmitter Section 5 Warnings Faults 126 ...
Page 129: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 127 6 Specifications ...
Page 152: ...XNX Universal Transmitter Section 6 Specifications 150 Figure 232 XNX BT Configuration ...
Page 161: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 159 7 Control Drawings ...
Page 162: ...XNX Universal Transmitter Section 7 Control Drawings 160 7 1 XNX UL INMETRO ...
Page 163: ...XNX Universal Transmitter Section 7 Control Drawings 161 ...
Page 164: ...XNX Universal Transmitter Section 7 Control Drawings 162 ...
Page 165: ...XNX Universal Transmitter Section 7 Control Drawings 163 7 2 XNX UL CSA FM ...
Page 166: ...XNX Universal Transmitter Section 7 Control Drawings 164 ...
Page 167: ...XNX Universal Transmitter Section 7 Control Drawings 165 ...
Page 192: ...XNX Universal Transmitter Appendix B Modbus Protocol 190 ...
Page 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Appendix C Warranty ...
Page 195: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 193 Index ...
Page 199: ......