XNX Universal Transmitter
Section 6 - Specifications
134
FOOTNOTES (
SEE TABLE ON PREVIOUS PAGE
):
1� Accuracy of reading at default Alarm 1 concentration (typically 10%FS or defined minimum alarm level setting, whichever greater) when operated at default full scale�
2� System conditioning may be required to achieve stated results� Contact Honeywell Analytics for details�
3� Measured using calibration flow housing at calibration flow rate (300-375 ml/min) with dry gas�
NOTES (
SEE TABLE ON PREVIOUS PAGE
):
• Data taken at ambient conditions of 20°C, 50% RH�
• Data represents typical values of freshly calibrated sensors without optional accessories attached�
• Performance figures are measured by test units calibrated at 50% of full scale�
• Standard temperature range for XNX EC Sensors is -20°C to +55°C; ATEX, IECEx�
• Extended temperature ranges for the XNX EC Sensors are -40°C to -20°C
• Accuracy between the temperatures of -40°C and -20°C is ±30% at the applied gas concentration�
• Operating the XNX EC Sensors at extended temperature ranges for a prolonged time period exceeding 12 hours may cause deterioration in sensor performance and shorter
sensor life�
• Barometric pressure effects on the O
2
sensor: The output from the O
2
sensor has pressure effects of <0�1% change of output per % change in pressure� When the barometric
pressure changes by ±20% the output from the O
2
sensor changes <±0�4%Vol� However, the oxygen sensor shows transient behavior when subjected to a rapid change in
ambient pressure due to either weather or altitude� For example, a 10KPa instantaneous positive pressure step change may cause an overscale alarm condition for a period
of about 12 seconds�
• Recalibration is recommended if the temperature of local environment has varied by more than ±15°C from the temperature of calibration�
• Response times may increase at lower temperatures�
• Contact Honeywell Analytics for any additional data or details�
Summary of Contents for XNX
Page 1: ...Technical Manual XNXTM Universal Transmitter ...
Page 2: ......
Page 6: ...XNX Universal Transmitter Table of Contents 4 Table of Contents ...
Page 11: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 9 1 Introduction ...
Page 91: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 89 3 Calibration ...
Page 104: ...XNX Universal Transmitter Section 3 Calibration 102 ...
Page 105: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 103 4 Maintenance ...
Page 128: ...XNX Universal Transmitter Section 5 Warnings Faults 126 ...
Page 129: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 127 6 Specifications ...
Page 152: ...XNX Universal Transmitter Section 6 Specifications 150 Figure 232 XNX BT Configuration ...
Page 161: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 159 7 Control Drawings ...
Page 162: ...XNX Universal Transmitter Section 7 Control Drawings 160 7 1 XNX UL INMETRO ...
Page 163: ...XNX Universal Transmitter Section 7 Control Drawings 161 ...
Page 164: ...XNX Universal Transmitter Section 7 Control Drawings 162 ...
Page 165: ...XNX Universal Transmitter Section 7 Control Drawings 163 7 2 XNX UL CSA FM ...
Page 166: ...XNX Universal Transmitter Section 7 Control Drawings 164 ...
Page 167: ...XNX Universal Transmitter Section 7 Control Drawings 165 ...
Page 192: ...XNX Universal Transmitter Appendix B Modbus Protocol 190 ...
Page 193: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 191 Appendix C Warranty ...
Page 195: ...XNX Universal Transmitter XNX Universal Transmitter Technical Manual 193 Index ...
Page 199: ......