background image

 

SRC-C1  

 

Doc: 70-07-0220, V1.2, 20170131, Subject to alteration, ©Vector Controls GmbH, Switzerland, www.vectorcontrols.com 

Page 1 

 

 

SRC-C1 Indoor CO2 Transmitter 

Features 

 

Indoor CO2 measurement 

 

Indication with three color led 

 

Minimum and maximum value memory 

 

0…10 V, 0…20 mA or 2…10 V, 4…20 mA measuring signals selectable 

with jumpers 

 

Optional alternative signal ranges programmable 

 

May be used as simple P-controller  

 

Selectable averaging signal

 

 

Optional external display (OPU-S)

 

 

Status LED

 

Applications 

 

Indoor CO2 measurement 

 

Recording of minimum and maximum limits for critical environments 

 

Direct control of extraction fan 

CO2 transmitter 

The CO2 concentration is measured through non-dispersive infrared (NDIR) waveguide technology with ABC automatic 

background calibration algorithm. The applied measuring technology guarantees excellent reliability and long term stability. 

The microprocessor samples the CO2 once per second. It calculates an averaging signal over a preset number of seconds and 

generates the output signal.  

The output signal range and type may be customized by jumpers and if required by a programming tool. Standard signal 

ranges are 0-10 VDC, 2-10 VDC, 4-20 mA and 0-20 mA. These ranges can be set by jumpers. Other ranges can be set by 

using the external display and programming module. (OPU-S) 

Automatic Baseline Calibration (ABC) 

The ABC background calibration constantly supervises the measured CO2 concentrations. The calibration function expects the 

CO2 values sink to 400 ppm when the room is not occupied. Over a period of several days the controller tries to reach this 

value step by step through recalibration of 30ppm per day max. In order to reach the given accuracy, it is required that the 

Sensor is for at least 3 weeks in operation.  

 

Note

: The ABC calibration works only in those applications where the CO2 concentration sinks regularly to fresh air levels of 

400 ppm. For special applications such as green houses, animal farms, etc. the ABC calibration should be de-activated and 

the sensor should be manually calibrated. The automatic calibration can be deactivated through the external operation 

terminal. The Sensor can be calibrated by the client and does not need to be sent in for calibration. See last page for details.  

Minimum and maximum values:  

Using a display & programming accessory, the user has the option to read out and reset minimum and maximum values. The 

minimum and maximum values may as well be used as output signals. The minimum and maximum values are saved into the 

EEPROM and are available after a power interruption.  

Indication of air quality indication:  

A three color LED is used to indicate air quality: Green light for low CO2 concentration, orange light for medium and red light 

for high concentration. The levels for low-medium-high may be programmed.  

Default settings are: CO2 > 0 ppm = low, CO2 > 800 ppm = medium, CO2 > 1500 ppm = high.  

Ordering 

Item name 

Item code 

Description/option 

SRC-C1 

40-30 0062 

CO2 transmitter 

Accessories 

Item name 

Item code 

Description/option 

OPU-S 

40-50 0006 

External display module.  

For the correct display of values V1.4 and later is required 

Reviews: