LCN System Installation
5-3
9/96
5.3
5.3 WIRING RECOMMENDATION—ERGONOMIC UNIVERSAL STATION
The ergonomic Universal Station is designed to accommodate conduit access from the rear
of the station or from beneath the floor.
•
Figure 5-3 shows access from the rear of the station.
•
Figure 5-4 shows access from beneath the station.
•
Figure 5-5 show the interior of the connection box.
Wiring entry to an ergonomic Universal Station can be made from the rear or through the
1 1/2” hole in the cabinet. The following conduit parts were used in the design of the
access.
Table 5-1 — Conduit Parts for Installation of an Ergonomic Universal Station
Function
Source
Part Number
3/4” 90
°
Pulling Elbow Male to Female
Appleton
MFL-75
Bridgeport
72-DC
Midwest/Cooper
811
O-Z/Gadney
MF-075
RACO
2663
3/4” Zinc Die Cast Screw-in Connector with Steel
Locknut
Appleton
SGC-75DC
Bridgeport
521-DC
Midwest/Cooper
772
O-Z/Gadney
RACO
3/4” Clamp Connector for Onmetallic Sheathed and
Flexible Wire
Honeywell
51190714
•
Wiring should be AWG 14-3/2.5 mm2 or larger for greater cable lengths. See TPS
System Site Planning.
SERVICE
BREAKER SIZE
120 Vac
15 Amp
240 Vac
15 Amp
Summary of Contents for TotalPlant LCN
Page 1: ...LCN System Installation SW20 500 ...
Page 2: ......
Page 3: ...LCN Installation LCN System Installation SW20 500 Release 510 CE Compliant 9 96 ...
Page 10: ...LCN System Installation iv 9 96 ...
Page 16: ...LCN System Installation 2 4 9 96 ...
Page 42: ...LCN System Installation 4 6 9 96 ...
Page 50: ...LCN System Installation 6 2 9 96 ...
Page 58: ...LCN System Installation 8 6 9 96 ...
Page 60: ...LCN System Installation 9 2 9 96 ...
Page 68: ...LCN System Installation 11 2 9 96 ...
Page 70: ...LCN System Installation 12 2 9 96 ...
Page 83: ...LCN System Installation 15 5 9 96 15 7 15052 Figure 15 6 Mounting of an Two LCN MAUs ...
Page 84: ...LCN System Installation 15 6 9 96 ...
Page 112: ...LCN System Installation B 6 9 96 ...
Page 128: ...LCN System Installation Index 4 9 96 ...
Page 130: ......
Page 131: ......