65-0315—02
44
DHW storage
enable
Enabled, Disabled
11
17
Storage time ___hour ___min ___sec
Setpoint
-40 °F to 266 °F
(-40 °C to 130 °C)
Off hysteresis -0 °F to 180 °F (-17 °C to 82 °C)
On hysteresis -0 °F to 180 °F (-17 °C to 82 °C)
Tap detect
degrees
-0 °F to 180 °F (-17 °C to 82 °C) 12
17
Tap detect on
recognition
time
___hour ___min ___sec
Tap detect on
threshold
-0 °F to 180 °F (-17 °C to 82 °C)
Tap detect
minimum on
time
___hour ___min ___sec
Tap stop
inlet-DHW
degrees
-0 °F to 180 °F (-17 °C to 82 °C)
Tap stop
outlet-Inlet
degrees
-0 °F to 180 °F (-17 °C to 82 °C)
Plate preheat
setpoint
-40 °F to 266 °F
(-40 °C to 130 °C)
Plate preheat
on
recognition
time
___hour ___min ___sec
Plate preheat
on hysteresis
-0 °F to 180 °F (-17 °C to 82 °C)
Plate preheat
off hysteresis
-0 °F to 180 °F (-17 °C to 82 °C)
Plate preheat
detect on
threshold
-0 °F to 180 °F (-17 °C to 82 °C)
Plate preheat
detect off
threshold
-0 °F to 180 °F (-17 °C to 82 °C)
Plate preheat
minimum on
time
___hour ___min ___sec
Plate preheat
delay after
tap
___hour ___min ___sec
Warm
Weather
Setpoint
Enable
Enabled, disabled
13
18
Warm
Weather
Setpoint
-40 °F to 266 °F
(-40 °C to 130 °C)
Table 60. Configurable Parameters. (Continued)
Parameter
Comment
Table
#
Page
#
CH maximum
modulation
rate
RPM or %
14
18
DHW
maximum
modulation
rate
RPM or %
Minimum
modulation
rate
RPM or %
CH forced
rate time
0-600 seconds
CH forced
rate
RPM or %
DHW forced
rate time
0-600 seconds
DHW forced
rate
RPM or %
CH slow start
enable
Enabled
Disabled
DHW slow
start enable
Enabled
Disabled
Slow start
degrees
-40 °F to 266 °F
(-40 °C to 130 °C)
Slow start
ramp
RPM /minute or %/minute
0-10/4-20 mA Output hysteresis
0-10/4-20 mA
Output
hysteresis
4-20 mA
input
hysteresis
Pump control Auto
On
16
19
Pump output Pump A
Pump B
Pump C
None
Pump start
delay
___hour ___min ___sec
Overrun time ___hour ___min ___sec
Boiler pump
output
Pump A
Pump B
Pump C
None
Table 60. Configurable Parameters. (Continued)
Parameter
Comment
Table
#
Page
#