65-0315—02
14
Most of this configuration is performed by either the
contractor/installer or at Honeywell. Each functional group is
displayed on the Configuration menu page.
Parameters in functional groups that are not applicable for the
installation can be ignored. In some cases, features in a
functional group are disabled by default and are enabled when
needed for the installation.
R7910 HYDRONIC CONTROL,
R7911 STEAM CONTROL
CONFIGURATION
PARAMETERS
The following pages list the configuration parameters available
for the R7910 or R7911 installed.
NOTE: Individual Configuration pages may differ from
this text as features are added or amended by
Honeywell.
A password is required to make changes to the Configuration
Parameters. The SOLA Control will be in a Lockout 2 “waiting
for safety data verification” as received or will go to a Lockout
2 when changes are made to the safety data.
WARNING
Explosion Hazard.
Improper configuration can cause fuel buildup and
explosion.
Improper user operation may result in PROPERTY
LOSS, PHYSICAL INJURY or DEATH.
The OI Display used to change parameters, must be
attempted by
only experienced and/or licensed
burner/boiler operators and mechanics
.
Fig. 30. System identification and access configuration
(Hydronic Screen Shown).
Table 5 displays System Identification and Access
parameters.
When the burner name is changed, the name is saved in the
R7910 or R7911 and displayed in the title of all pages that
zoom into the control.
Default parameter settings for installer and Honeywell
passwords are “sola” and “solaoem,” respectively. These
passwords most likely have been changed by Honeywell.
Factory Data gives Honeywell an option to display a brand
name other than Sola on this configuration page. Additional
information displayed on this page is listed in Table 6.
Pump Configuration
Stack Limit
Statistics Configuration
Annunciation Configuration
High Limit
Burner Control Interlocks
Stack Limit
Burner control Timings and
Rates
Delta T Limits
T-Rise Limit
Heat Exchanger High Limit
Anti-condensation
Burner Control Flame Failure
Frost Protection
Configuration
System Configuration
Annunciation Configuration
Fan Configuration
Burner Control Interlocks
Lead Lag Configuration
Burner Control Timings and
Rates
Burner Control Ignition
Burner Control Flame Failure
System Configuration
Fan Configuration
Sensor Configuration
Lead Lag Slave
Configuration
Lead Lag Master
Configuration
Table 4. Functional Configuration Groups.
Hydronic Control
Steam Control
Table 5. System Identification and Access Parameters.
Parameter
Comment
Boiler Name
Name to identify boiler (up to 20
characters)
Installation
Notes regarding installation (up to 20
characters)
Installer password
Change installer password setting
OEM password
Change OEM password setting
Factory Data
OEM name to associate with boiler
(up to 20 characters)