65-0315—02
Safety Parameter Verification
When any of the safety configuration parameters are
changed, the safety parameter verification procedure must be
performed before the control will resume burner control. The
control enters a lockout state, if not already in one, and
remains locked out until this verification procedure is
performed.
Safety parameter verification lockout occurs when safety
parameter setting is changed. See Fig. 48.
Fig. 48. Safety verification lockout.
The user must log in before verification can be completed, as
shown in Fig. 49.
Fig. 49. Safety verification login.
After successful login, the user presses the Begin button to
start safety parameter verification. See Fig. 50.
Fig. 50. Begin safety verification.
The first group of safety configuration parameters that needs
verification is displayed. The user is asked to confirm that the
settings are correct, as shown in Fig. 51.
Fig. 51. Confirm safety parameter settings.
Table 29. Burner Control Flame Failure
Configuration.
Parameter Comment
Ignite failure
response
Lockout
Recycle
Recycle & hold
Recycle & lockout
Ignite failure delay
___hour ___min ___sec
Ignite failure retries
1, 3, or 5
MFEP flame failure
response
Recycle
Lockout
Run flame failure
response
Recycle
Lockout
Fan speed error
response
Recycle
Lockout