65-0315—02
32
Fig. 68. DHW Hydronic Status menu (bottom).
Burner Control Status
The Burner Control status page will display the status data
shown in Table 46.
The bar graph displayed for this status is the outlet sensor
temperature.
Fig. 69. Burner Control Status menu (top).
Fig. 70. Burner Control Status menu (bottom).
Burner control can be turned on and off in the R7910 or
R7911 by the user.
Table 46. Burner Control Status.
Data Comment
Alarm reason
Description for alarm being on (maybe
lockout or a hold message)
Annunciator first out First annunciator input related to
lockout
Annunciator hold
First annunciator input related to hold
Burner state
Disabled, Locked out, Anti-short cycle,
Unconfigured safety data, Standby
Hold, Standby, Delay, Normal
Standby, Preparing, Firing, Postpurge
Sequence time
Running time for timed burner control
operation (seconds)
Delay time
Running display of delay time when
burner control in delay state.
Firing rate
% or RPM. Adjustable when firing rate
control set to Manual.
Firing rate control
Auto or Manual
Flame signal
Flame signal strength
Hold code
Description of hold message if locked
out
Lockout
Description of lockout message if
locked out
Pilot test hold
Off or Hold
Remote STAT
On or Off
Note: Steam will show Steam psi as the bar graph