65-0315—02
26
After the first safety parameter group has been confirmed by
the user (by pressing the Yes button), the next safety
parameter group waits for verification as shown in Fig. 52.
Fig. 52. Safety parameter settings confirmed; next group
waiting for confirmation.
The user has 30 secs to confirm each safety configuration
group’s settings. If the user takes too long to confirm the
settings, an error message is displayed, as shown in Fig. 53.
Fig. 53. Confirmation timed out.
After all safety parameter groups have been verified, the user
must press the Reset button on the control within 30 seconds
to confirm the correct device. See Fig. 54.
Fig. 54. Reset R7910 or R7911.
When the user has pressed the Reset button on the control,
completing verification procedure, a Verification Complete
screen is displayed, as shown in as shown in Fig. 55.
Fig. 55. Safety parameter configuration complete.
If for some reason the user does not press the Reset button
on the control within 30 seconds, the configuration is
cancelled, as shown in Fig. 56.
Fig. 56. Control reset timed out.