DHW Storage Configuration
Table 11 displays DHW Storage configuration parameters.
DHW Plate Heat Exchanger
Configuration
Table 12 displays DHW Plate Heat Exchanger configuration
parameters.
Table 10. Domestic Hot Water (DHW)
Configuration Parameters.
Parameter
Comment
Enable
Disable or Enable Domestic Hot Water
Loop
Demand switch
Sensor for Central Heat demand:
DHW sensor only,
DHW sensor & Remote Stat,
DHW switch & inlet sensor, or
DHW switch & outlet sensor
Priority source
Which system has priority:
Disabled or
Heat Demand
Priority method
Boost during priority time
Drop after priority time
Modulation sensor
DHW Sensor
Outlet Sensor
Inlet Sensor
Auto: DHW (S6) or Inlet Sensor
Auto: DHW (S6) or Outlet Sensor
Setpoint
-40 °F to 240 °F (-40 °C to 115 °C)
Time of day setpoint Setpoint when Time Of Day switch is
on. -40 °F to 240 °F (-40 °C to 115 °C)
Off hysteresis
Differential above setpoint when boiler
is turned off. -40 °F to 240 °F (-40 °C
to 115 °C)
On hysteresis
Differential from setpoint when boiler
is turned on.
2 °F to 234 °F (-16 °C to 112 °C)
DHW priority
override time
___hour ___min ___sec
Hysteresis step
time
___hour ___min ___sec
DHW priority vs CH Which system has priority:
Central Heat over Domestic Hot
Water, or
Domestic Hot Water over Central Heat
DHW priority vs
Lead Lag
Which system has priority:
Lead Lag over Domestic Hot Water,
Domestic Hot Water over Lead Lag
DHW P-gain
Gain applied for the P portion of the
PID equation
0-400
DHW I-gain
Gain applied for the I portion of the
PID equation
0-400
DHW D-gain
Gain applied for the D portion of the
PID equation
0-400
Table 11. DHW Storage Configuration Parameters.
Parameter
Comment
DHW storage
enable
Enabled, Disabled
Storage time
___hour ___min ___sec
Setpoint
32 °F to 250 °F (0 °C to 120 °C)
Off hysteresis
0 °F to 234 °F (-17 °C to 112 °C)
On hysteresis
0 °F to 234 °F (-17 °C to 112 °C)
Table 12. DHW Plate Heat Exchanger
Configuration Parameters.
Parameter
Comment
Tap detect degrees -0 °F to 180 °F (-17 °C to 82 °C)
Tap detect on
recognition time
___hour ___min ___sec
Tap detect on
threshold
-0 °F to 180 °F (-17 °C to 82 °C)
Tap detect minimum
on time
___hour ___min ___sec
Tap stop inlet-DHW
degrees
-0 °F to 180 °F (-17 °C to 82 °C)
Tap stop outlet-Inlet
degrees
-0 °F to 180 °F (-17 °C to 82 °C)
Plate preheat
setpoint
-40 °F to 266 °F (-40 °C to 130 °C)
Plate preheat on
recognition time
___hour ___min ___sec
Plate preheat on
hysteresis
-0 °F to 180 °F (-17 °C to 82 °C)
Plate preheat off
hysteresis
-0 °F to 180 °F (-17 °C to 82 °C)
Plate preheat detect
on threshold
-0 °F to 180 °F (-17 °C to 82 °C)
Plate preheat detect
off threshold
-0 °F to 180 °F (-17 °C to 82 °C)
Plate preheat
minimum on time
___hour ___min ___sec
Plate preheat delay
after tap
___hour ___min ___sec