65-0315—02
20
Statistics Configuration Parameters
Table 17 displays Statistics configuration parameters.
Fig. 37. Statistics configuration.
High Limit Configuration Parameters
(R7910 Hydronic Control Only)
Table 18 displays outlet high limit configuration parameters.
Fig. 38. High Limits configuration.
Stack Limit Configuration
Parameters
Table 19 displays stack limit configuration parameters.
Fig. 39. Stack Limit configuration.
Table 17. Statistics Configuration Parameters.
Parameter
Comment
Auxiliary pump cycles 0-999,999
Boiler pump cycles
0-999,999
Burner cycles
0-999,999
Burner run time
0-999,999
CH pump cycles
0-999,999
DHW pump cycles
0-999,999
System pump cycles 0-999,999
Auxiliary 2 pump
cycles
0-999,999
Table 18. High Limit Configuration Parameters.
Parameter
Comment
DHW high limit
Enabled
Disabled
DHW high limit
response
Recycle & hold
Lockout
DWH high limit
setpoint
32 °F to 250 °F (0 °C to 121 °C)
Outlet high limit
Enabled
Disabled
Outlet high limit
response
Recycle & hold
Lockout
Outlet high limit
setpoint
32 °F to 250 °F (0 °C to 121 °C)
Table 19. Stack Limit Configuration Parameters.
Parameter Comment
Stack limit
Enabled dual sensor safety
Enabled single sensor non safety
Disabled
Stack limit delay
___hour ___min ___sec
Stack limit response Lockout
Recycle & delay
Stack limit setpoint
32 °F to 266 °F (0 °C to 130 °C)