OPERATION
6
115
RM640
www.honeywellprocess.com
34-VF-25-131 iss.1 GLO Feb 2019 US
Description of errors and corrective actions
Status
type
Error message
Description
Corrective action
F
F
F
F
Sensor
Sensor
Sensor
Sensor
Corrupt Sensor Parameter
The sensor memory is bad.
De-energize and then energize the
device again.
If the message is shown again, tell
the supplier.
No Signal
There is no signal from the
antenna or the antenna signal is
too weak for a long time.
Do a check of the device
installation. For more data about
installation, refer to the handbook.
If the message is shown again, tell
the supplier.
Microwave Tuning Voltage Error
A microwave error occurred.
De-energize and then energize the
device again.
If the message is shown again, tell
the supplier.
Sensor Comm. Error
Internal bus communication error
or hardware failure.
No measurement value
The converter receives no
measurement data for a long time.
Do a check of the device
installation. For more data about
installation, refer to the handbook.
If the message is shown again, tell
the supplier.
F
F
F
F
Electronics
Electronics
Electronics
Electronics
Fatal Converter Error (DM)
1
An electronics or hardware failure
occurred.
De-energize and then energize the
device again.
If the message is shown again, tell
the supplier.
Fatal Converter Error (CO)
2
An electronics or hardware failure
occurred.
Fatal Converter Error (Generic)
An electronics or hardware failure
occurred.
CO Safety Reaction
3
Current Output Safety Reaction.
This error message is shown if the
current output is less than 3.6 mA
or more than 21 mA.
Do a check for other error
messages.
Internal Comm. Error
Internal bus communication error. De-energize and then energize the
device again.
If the message is shown again, tell
the supplier.
Power Supply Error
Internal voltage is too low to
energize the sensor.
Check the electrical connections
to the power supply connection or
replace the converter.
Internal voltage is too high.
Sensor/Conv. FW Mismatch
The sensor firmware version does
not agree with the converter
firmware version. This can be
caused by a bad firmware update.
De-energize and then energize the
device again.
If the message is shown again, tell
the supplier.
Max. Number of Restarts
The device could not start the
measuring mode after a given
number of times that the device
was de-energized and then
energized again.
Do a check of the power supply.
Inconsistent Parameters
Internal bus communication error. De-energize and then energize the
device again.
If the message is shown again, tell
the supplier.
Sensor Comm. Error
Internal bus communication error
or hardware failure.
Summary of Contents for RM640
Page 4: ...4 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ABOUT THIS DOCUMENT RM640 ...
Page 20: ...1 SAFETY INSTRUCTIONS 20 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...
Page 56: ...4 ELECTRICAL CONNECTIONS 56 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...
Page 120: ...6 OPERATION 120 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...
Page 182: ...10 APPENDIX 182 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...
Page 183: ...APPENDIX 10 183 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...