Using WIN-PAK with NetAXS-123
Configuration Guidelines
NetAXS-123 Access Control Unit User’s Guide
,
Document 800-05168, Revision B
75
Table 3-2
lists the factory I/O board default settings for Door #2. These mappings
should be used for the readers, inputs, and outputs when either a 1- or 2-door I/O
board is attached to the board-to-board connector on the controller board.
Table 3-2:
Factory Default Configuration Settings for Door 2
Type
Purpose
Logical Number
Other
Reader A
Reader B
a
a. Reader B is not available in WIN-PAK.
Input
Egress
9
9
Status
10
10
Reader Tamper
11
12
Output
Lock Relay
7
7
Reader LED
8
8
Aux Relay
9
b
b. This output may not be controlled from WIN-PAK. However, you may config-
ure custom commands to control it.
Reader Buzzer
10
b
10
b