Configuring via the Web Server
Configuring Interlocks
NetAXS-123 Access Control Unit User’s Guide
,
Document 800-05168, Revision B
69
To create an interlock
:
1. Click
New Interlock
to display the screen.
2. Use the descriptions in
Table 2-14
to configure the interlock:
3. Click
Add Interlock
to create the interlock.
To delete an interlock
:
1. In the Int Lk column, click the number of the interlock you want to delete.
2. Click
Delete Interlock
to display the Delete Interlock screen, and click
OK
to
complete the deletion.
Table 2-14:
Configuration > Interlocks Fields
Interlock element
Description
Trigger
Specifies the input, output, or output group for which a
change of state will cause a reaction from another input,
output, or group.
If Trigger = Inputs, then triggers 1-20 will have an
interlock link (Int Lnk) number from 1-20.
If Trigger = Outputs, then outputs 1-14 will have an
interlock link (Int Lnk) number from 97-110.
Use the drop-down list to specify the number of the input
or output.
Reacting Component
Specifies the input, output, or output group that will react
to a change of state from the trigger point. Use the
drop-down list to specify the number of the input or
output.
Reacting
Component’s Action
Upon Trigger Alarm
– Specifies the reacting
component’s action when the trigger’s change of state
occurs. Select the action from the Upon Trigger Alarm
drop-down list.
Upon Trigger Normal
– Specifies the reacting
component’s action when the trigger’s change of state
occurs. Select the action from the Upon Trigger Normal
drop-down list.
Following are the available actions in the drop-down lists:
When Reacting Component = Input,
then actions are No Action, Shunt, Unshunt, Timed
Shunt, Follow, and Invert Follow.
When Reacting Component = Output,
then actions are No Action, Energize, De-Energize, Pulse
On, Pulse Off, Follow, and Invert Follow.
Interlocking is an advanced functionality. Contact
Technical Support for information on how to use it.
Summary of Contents for NetAXS-123
Page 6: ...vi www honeywell com ...
Page 10: ...NetAXS 123 Access Control Unit User s Guide Document 800 05168 Revision B x ...
Page 112: ...102 www honeywell com Using WIN PAK with NetAXS 123 Standalone Commands ...
Page 128: ...118 www honeywell com Monitoring NetAXS 123 Status Monitoring System Status ...
Page 138: ...128 www honeywell com File Management Generating Reports ...
Page 162: ...152 www honeywell com Clearing the Cache ...
Page 166: ...156 www honeywell com ...