100
www.honeywell.com
Using WIN-PAK with NetAXS-123
Standalone Commands
3.8.5 C (Card Delete) Command
_C=pn_code<CR>
Variables:
pn = panel number (1-31)
code = card number (range depends on card format)
Example #1:
_C=6_12345<CR>
This command would remove card 12345 from panel 6.
Example #2:
_C=18_52989<CR>
This command would remove card 52989 from panel 18.
3.8.6 W (Input) Command
_W=pn_input_{SO | SC | NO | NC}<CR>
Variables:
SO: Supervised normally open
SC: Supervised normally closed
NO: Non-supervised normally open
NC: Non-supervised normally closed (default)
Example:
_W=1_9_SO<CR>
Input 9 has been programmed as supervised, normally open on panel 1.
3.8.7 P (Interlock) Command
_P=pn_I/O_[number]_I/O [number]_ {D | E | F | N | P}_{D | E | F | N | P}<CR>
Parameters:
number: for an input number, the range is 1-16; for output, 1-14
D: De-energize
E: Energize
F: Follow
N: No action
P: Pulse
Example:
_P=1_I_5_O_3_E_D<CR>
When Input 5 is triggered, Output 3 energizes.
When Input 5 returns to its normal state, Output 3 de-energizes.