Synchronization Detail Chart
Synchronization
Primary panel to the Secondary panel synchronization occurs at the time the Secondary
panels are "Registered" with the Primary.
The Synchronization only occurs at the time of panel registration and will include Common
Data.
The Secondary panel will reboot after synchronization.
Example:
Primary to Secondary Synchronization in following order with (3) Secondary Panels:
1. The 1st Secondary panel will receive the backup and reboot.
2. The 2nd Secondary panel will receive the backup and reboot
3. The 3rd Secondary panel will receive the backup and reboot.
Common data includes:
•
Schedules
•
Cards
•
Card Formats
•
Holidays
•
Access Group Name (access group details are panel-specific)
•
Configuration (Site Codes)
Access control behavior during synchronization:
•
Primary Panel access control not affected.
•
Newly registered secondary panels will show online in Web Interface and will
keep its existing card and common configure. Once common data received,
secondary access control and communication processes stop running and
the existing common data will be overwritten by new one from primary. Once
the common data is received the Secondary panel will reboot.
•
Approximately 4 minutes for secondary panel access control to function after
registration and synchronization.
Summary of Contents for MPA1
Page 1: ...Document 800 26311_Rev B July 2020 Access Control Unit MPA1 User Guide ...
Page 14: ... 13 Document 800 26311_ A April 2020 This page is intentionally left blank ...
Page 72: ... 75 Document 800 26311_ A April 2020 This page is intentionally left blank ...
Page 100: ...www honeywell com security 104 MPA1 User Guide This page is intentionally left blank ...