Interlock
Actions
Then Execute (Alarm Action)
– Specifies the reacting
component’s action when the trigger’s change of state occurs.
Select the action from the available options.
Upon Resuming
(Normalcy)
– Specifies the reacting
component’s action when the trigger returns to the normal state.
Select the action from the available options.
Following are the available Input Reactor actions in the
drop-down lists:
Unshunt
– Reactivates the input point.
Shunt
– Ignores alarms from the input point.
Follow
– The reacting point (second point) takes on the same
state as the triggering point (first point).
Invert Follow
– The reacting point (second point) takes on the
opposite state as the triggering point (first point).
No action
– The reacting point (second point) does nothing in
response to the state change of the triggering point (first point).
No change of state.
Timed Shunt
– Ignores alarms from the input point for a
specified amount of time.
Following are the available
Output Reactor
actions in the
drop-down lists:
De-energize
– Remove energy from an output point or group. On
a system, the normal state of an output point or group is
"de-energized".
Energize
– The state of an output point or group. Output points
and groups are in a normal state when they are "de-energized". An
energized state means that the output or group is active.
Follow
– The reacting point (second point) takes on the same
state as the triggering point (first point).
Invert Follow
– The reacting point (second point) takes on the
opposite state as the triggering point (first point).
No action
– The reacting point (second point) does nothing in
response to the state change of the triggering point (first point).
No change of state.
Pulse
– Energizes the output point or group for a specific amount
of time.
Pulse Off–
Becomes unshunted for the programmed shunt time,
followed by a return to the shunted state.
Configuration
Description
Summary of Contents for MPA1
Page 1: ...Document 800 26311_Rev B July 2020 Access Control Unit MPA1 User Guide ...
Page 14: ... 13 Document 800 26311_ A April 2020 This page is intentionally left blank ...
Page 72: ... 75 Document 800 26311_ A April 2020 This page is intentionally left blank ...
Page 100: ...www honeywell com security 104 MPA1 User Guide This page is intentionally left blank ...