MPA1 User Guide
Four inputs are associated with each of the doors on a MPA1 panel:
•
Status
– Provides door status information (DrCnt).
•
Egress
– Allows the door to open or close normally without generating an alarm (REX).
•
Tamper A
– Reports abnormal handling of the reader device or wiring for Reader A.
•
Tamper B
– Reports abnormal handling of the reader device or wiring for Reader B.
The Inputs tab allows you to configure the following settings for each door:
•
Define the Status, Egress, and Tamper input modes.
•
Specify the Status, Egress, and Tamper shunt time, or the period of time the door’s
normal state will be ignored.
•
Specify the Status, Egress, and Tamper debounce time, or the period of time the input
must remain in its new state before it is recognized as being in the new state.
•
Specify the schedules for the Status, Egress, and Tamper inputs.
•
Enable or disable Auto-Relock for the Status inputs.
1. Click
Inputs
on the
Doors
configuration window to open the Inputs configuration
pane.
Figure 2-26 Door Inputs Configuration Interface
2. Enter an
Input Name
.