4. Configure
Shunt
and
Debounce
times.
5. Configure
Scheduling
.
6. Click
Save
.
Configuring Outputs
In the Individual Outputs tab, you can configure the following for each output:
•
Pulse time
•
Disable/Enable Latch and Interlocks
•
Energized and Disable Interlocks schedules
Configuration
Description
Shunt Time
(h:m:s)
Specifies the amount of time for which the inputs are shunted, or
de-activated. The maximum length of time is 1 hour, 45 minutes,
59 seconds.
You can express seconds in tenths of a second.
Debounce Time
(sec)
Specifies the period of time (MIN = 0 second, MAX = 6553.5
seconds) the input must remain in a new state before generating
an alarm. For example, with a 5-second debounce time selected,
if a Normal state is changed to Alarm, the state must remain in
Alarm for five consecutive seconds before an alarm is generated.
Configuration
Description
Shunt Schedule
Specifies the time period during which the input will be ignored.
Disable
Interlocks
Specifies the time period during which the programmed action on
this input from another point will be disabled.
Disable Alarm
Messages
Specifies the time period during which Alarm and Normal will not
be reported, but Short and Cut will be reported.
Short
alarms are
triggered when a short occurs in the system.
Cut
alarms are
triggered when a wire is cut.
Summary of Contents for MPA1
Page 1: ...Document 800 26311_Rev B July 2020 Access Control Unit MPA1 User Guide ...
Page 14: ... 13 Document 800 26311_ A April 2020 This page is intentionally left blank ...
Page 72: ... 75 Document 800 26311_ A April 2020 This page is intentionally left blank ...
Page 100: ...www honeywell com security 104 MPA1 User Guide This page is intentionally left blank ...